{ "Library": "cwlsxxa", "Description": "API for the Veris CWLSXXA CO2 Sensor Family", "Sensor Class": { "CWLXSSA": { "Name": "Veris CWLSXXA CO2 Sensor", "Description": "The driver was developed using the CWLSHTA CO2 Gas sensor. The 'T' variant supports a temperature transmitter, and the 'H' variant supports a humidity sensor. All 3 signals are provided by the device as analog 0-5Vdc, 0-10Vdc, or 4-20ma loop current outputs. For devices supporting temperature, the valid temperature range is 10C to 50C. The humidity ranges from 0% to 100% (non-condensing). The CO2 sensor ranges from 0 to 2000 ppm. This driver was developed using the 5Vdc outputs and the 4-20ma outputs. For voltage outputs, your MCU must be configured for 5V operation. In addition, you must configure the sensor (via it's configuration switches) to output 0-5VDC only. Using any other analog reference voltage will require the appropriate external circuitry (such as a voltage divider) in order to interface safely with your MCU. In addition, the sensor can be configured for 4-20ma usage, by specifying the correct receiver resistance (in ohms) in the constructor. This sensor was tested with a Cooking Hacks (Libelium) 4-channel 4-20ma Arduino interface shield. For this interface, the receiver resistance was specified as 165.0 ohms. For devices which do not support temperature, use '-1' as the temperature pin number in the object constructor. If temperature measurement is disabled, getTemperature() will always return 0C/32F. For devices which do not support humidity, use '-1' as the temperature pin number in the object constructor. If humidity measurement is disabled, getHumidity() will always return 0.", "Aliases": ["cwlsxxa"], "Categories": ["temp", "gaseous"], "Connections": ["analog"], "Project Type": ["industrial"], "Manufacturers": ["veris"], "Kits": [], "Examples": { "Java": ["CWLSXXA_Example.java"], "Python": ["cwlsxxa.py"], "Node.js": ["cwlsxxa.js"], "C++": ["cwlsxxa.cxx"], "C": [] }, "Specifications": { "Vsource (DC)": {"unit": "VDC", "low": 20, "high": 30}, "Vsource (AC)": {"unit": "VAC", "typ": 24}, "CO2 Measurement Range": {"unit": "ppm", "low": 0, "high": 5000}, "CO2 Accuracy": {"unit": "ppm ±", "typ": 30}, "CO2 Repeatability": {"unit": "ppm ±", "typ": 20}, "CO2 Response Time": {"unit": "s", "max": 60}, "RH Measurement Range": {"unit": "%", "low": 0, "high": 100}, "RH Operating Temperature Range": {"unit": "degC", "low": 10, "high": 35}, "RH Accuracy": {"unit": "%", "typ": 2}, "RH Stability": {"unit": "%", "typ": 1}, "Temperature Accuracy": {"unit": "degC", "typ": 0.5}, "Temperature Resolution": {"unit": "degC", "typ": 0.1}, "Temperature Range": {"unit": "degC", "low": 10, "high": 35} }, "Platforms": { "Intel Joule Module": { "Notes": ["Requires pull-up resistors with carrier board"], "Images": [""] } }, "Urls" : { "Product Pages": ["http://www.veris.com/Item/CWLSHTA.aspx"], "Datasheets": ["http://www.veris.com/docs/Datasheets/CDL_CDW_d0117.pdf"], "Schematics": [] } } } }